Voltage Drop in Long EV Charger Cables in Malaysia: Why Distance from DB to Charger Matters

By Alvin Wong, CEO of Innovative Green Power Sdn. Bhd.

When planning an EV charger installation, one question matters more than most: “How far is the charger from the distribution board (DB)?” That distance quietly determines how much voltage your charger receives — and how safely it performs for years to come.

​

At Innovative Green Power, we standardize every installation with 6 mm² full-copper cables as the minimum, and 10 mm² where higher loads or harsher conditions demand it.

​

​

Voltage Drop in Long Cables: Why Distance from DB to Charger — and Cable Size — Matters

​

1. Why voltage drop matters in EV charging

Voltage drop is the natural loss of voltage that occurs as electricity flows through a cable. The longer the cable or the higher the current, the greater the energy loss as heat.

​

For EV chargers drawing continuous current — sometimes for hours — even a small voltage drop can cause higher heat, slower charging, and wasted energy.

​

According to the Suruhanjaya Tenaga (ST) Guidelines for Electrical Wiring in Residential Buildings and IEC 60364-5-52, the maximum permissible voltage drop in any low-voltage circuit is 4 % of the supply voltage— roughly 9.2 V in Malaysia’s 230 V system.

​

​

2. The engineering standard: 6 mm² full-copper minimum

ST’s Guidelines on Electric Vehicle Charging System (2025) specify that every EV charger must be powered through a dedicated final circuit sized according to IEC 60364-5-52.

​

For most homes and condominiums, 6 mm² full-copper is the right balance of safety, performance, and compliance. It offers:

​

– Enough current-carrying capacity for continuous 32 A single-phase (7 kW) or 16 A three-phase (11 kW) chargers.

​

– Voltage-drop compliance even on moderate runs.

​

– Excellent thermal performance under Malaysia’s hot, humid conditions.

​

This makes 6 mm² the minimum standard for all professional installations — not an upgrade, but a safety requirement.

​

​

3. When to choose 10 mm² — and why

While 6 mm² covers most use cases, some conditions justify going one size up to 10 mm² full copper from the start:

​

– 22 kW three-phase chargers (≈ 32 A per phase) — the higher current demands thicker conductors for safe continuous duty.

​

– Full concealed wiring in concrete walls — reduced ventilation traps heat, so 10 mm² provides the necessary thermal margin.

​

– Long cable runs or high ambient temperatures — larger conductors reduce voltage drop and internal heating.

​

– Future scalability — if you plan to upgrade from 7 kW/11 kW to 22 kW later, installing 10 mm² now avoids re-wiring.

​

In simple terms:

​

– 7 kW or 11 kW charger → 6 mm² is usually enough.

– 22 kW charger or fully-concealed runs → start with 10 mm².

​

​

4. Why correct sizing matters more than “oversizing”

Using 10 mm² where it isn’t needed can create challenges:

​

– Many isolators, RCCBs and MCBs are rated for up to 6 mm² conductors. Larger cables may not fit without proper ferrules or upgraded terminals.

​

– Concealed conduits have space-factor limits (≈ 40 %); oversizing the cable may breach this rule or complicate pulling and bending.

​

– Bigger isn’t automatically safer if workmanship or containment isn’t adjusted accordingly.

​

That’s why IGP applies engineering judgement — upsizing where it adds safety, not merely thickness.

​

​

5. Real future-proofing: plan for 3-phase, not just thicker cable

If you intend to upgrade later to 11 kW or 22 kW three-phase, a single-phase cable won’t help. The correct way is to run a 5-core 6 mm² or 10 mm² copper cable from your DB, with matching isolator and conduit sizing. This ensures compliance today and flexibility for any 3-phase charger tomorrow.

​

​

6. IGP’s standard installation policy

– 6 mm² full-copper cable – baseline for all 7 kW (single-phase) and 11 kW (three-phase) chargers.

​

– 10 mm² full-copper cable – recommended for 22 kW chargers, fully-concealed routes in concrete, or runs beyond ≈ 20 m.

​

– Protection devices – Type A RCCB 40 A / 30 mA and MCB 40 A or as specified for three-phase.

​

– Testing and verification – voltage-drop measurement during commissioning and thermal scan for concealed runs.

​

This standard gives homeowners confidence that every installation meets both safety and performance benchmarks.

​

​

Closing Thought:

Voltage drop may be invisible, but its impact isn’t. Undersized cables overheat and waste energy. Oversized cables without planning cause installation challenges.

​

The solution is balanced engineering. At Innovative Green Power, we calculate, verify, and test every circuit. 6 mm² keeps you safe. 10 mm² keeps you ready.

Safe and Reliable EV Charging Systems, one at a time.